PT-2012-3550
CVE-2012-1802
·
تاريخ النشر
2012-04-18
·
تاريخ التحديث
2012-11-20
الوصف من
CVSS 2.0
7.8
عاليةالمقاييسAV:N/AC:L/Au:N/C:N/I:N/A:C
Name of the Vulnerable Software and Affected Versions
Siemens Scalance X Industrial Ethernet switch X414-3E versions prior to 3.7.1
Siemens Scalance X Industrial Ethernet switch X308-2M versions prior to 3.7.2
Siemens Scalance X Industrial Ethernet switch X-300EEC versions prior to 3.7.2
Siemens Scalance X Industrial Ethernet switch XR-300 versions prior to 3.7.2
Siemens Scalance X Industrial Ethernet switch X-300 versions prior to 3.7.2
Description
The issue is related to a buffer overflow in the embedded web server, which can be exploited by remote attackers using a malformed URL. This can cause a denial of service, resulting in a device reboot, or possibly allow the execution of arbitrary code.
Recommendations
For X414-3E versions prior to 3.7.1, update to version 3.7.1 or later.
For X308-2M versions prior to 3.7.2, update to version 3.7.2 or later.
For X-300EEC versions prior to 3.7.2, update to version 3.7.2 or later.
For XR-300 versions prior to 3.7.2, update to version 3.7.2 or later.
For X-300 versions prior to 3.7.2, update to version 3.7.2 or later.