PT-2012-5353 · Sielco Sistemi · Winlog Pro Scada+1
CVSS v2.0
4.3
متوسطة
| المتجه | AV:N/AC:M/Au:N/C:P/I:N/A:N |
Name of the Vulnerable Software and Affected Versions
Sielco Sistemi Winlog Pro SCADA versions prior to 2.07.17
Sielco Sistemi Winlog Lite SCADA versions prior to 2.07.17
Description
The issue allows remote attackers to read arbitrary files via port 46824 TCP packets. This is achieved by specifying a file-open operation with opcode
0x78 and a .. (dot dot) in a pathname, followed by a file-read operation with opcode 0x96, 0x97, or 0x98.Recommendations
For Sielco Sistemi Winlog Pro SCADA versions prior to 2.07.17, update to version 2.07.17 or later.
For Sielco Sistemi Winlog Lite SCADA versions prior to 2.07.17, update to version 2.07.17 or later.
استغلال
إصلاح
Path traversal
وجدت خطأً في الوصف؟ لديك ما تضيفه؟ لا تتردد في مراسلتنا 👾
تصنيف نقاط الضعف
المعرّفات ذات الصلة
المنتجات المتأثرة
Winlog Lite Scada
Winlog Pro Scada