PT-2014-1002

CVE-2014-2256

·

تاريخ النشر

2014-03-20

·

تاريخ التحديث

2020-02-10

الوصف من

CVSS 2.0
7.8
عالية
المقاييسAV:N/AC:L/Au:N/C:N/I:N/A:C
Name of the Vulnerable Software and Affected Versions Siemens SIMATIC S7-1200 CPU PLC devices with firmware prior to 4.0
Description The issue allows remote attackers to cause a denial of service, resulting in a defect-mode transition, via crafted ISO-TSAP packets. Exploitation can be achieved by sending a special TCP/IP packet to port 102, which can cause the device to transition into an emergency mode that lasts until a hardware reset is performed.
Recommendations For Siemens SIMATIC S7-1200 CPU PLC devices with firmware prior to 4.0, update the firmware to version 4.0 or later to resolve the issue.