PT-2019-6900

CVE-2013-2805

·

تاريخ النشر

2019-03-26

·

تاريخ التحديث

2020-02-10

الوصف من

CVSS 2.0
7.8
عالية
المقاييسAV:N/AC:L/Au:N/C:N/I:N/A:C
Name of the Vulnerable Software and Affected Versions Rockwell Automation RSLinx Enterprise Software versions CPR9 through CPR9-SR6
Description The issue arises from incorrect handling of input by the LogReceiver.exe service, resulting in a logic error when it receives a datagram with an incorrect value in the Record Data Size field. An attacker can exploit this by sending a modified datagram over Port 4444/UDP, causing an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot.
Recommendations For versions CPR9 through CPR9-SR6, apply the patches and follow the details provided in the Rockwell Automation Security Advisory to resolve the issue. As a temporary workaround, consider restricting access to Port 4444/UDP to minimize the risk of exploitation.
قابلية الاستغلال
إصلاح
التأثيرات
المورّدون
المنتجات المتأثرة
تصنيف نقاط الضعف
المعرّفات ذات الصلة
وجدت خطأً في الوصف؟ لديك ما تضيفه؟ لا تتردد في مراسلتنا 👾