PT-2022-10178

CVE-2021-32986

·

تاريخ النشر

2022-04-04

·

تاريخ التحديث

2022-10-25

الوصف من

CVSS 3.1
9.8
حرجة
المقاييسAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Name of the Vulnerable Software and Affected Versions Automation Direct CLICK PLC CPU Modules: C0-1x CPUs versions prior to v3.00
Description The issue arises when an authorized user unlocks the Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00. The unlocked state does not timeout, and if the programming software is interrupted, the PLC remains unlocked, allowing all subsequent programming connections without authorization. The PLC is only relocked by a power cycle or when the programming software disconnects correctly.
Recommendations For versions prior to v3.00, update the firmware to v3.00 or later to resolve the issue. As a temporary workaround, consider performing a power cycle after each use of the programming software to ensure the PLC is relocked. Additionally, ensure the programming software disconnects correctly to prevent unauthorized access.
قابلية الاستغلال
إصلاح
التأثيرات
المورّدون
المنتجات المتأثرة
المعرّفات ذات الصلة
وجدت خطأً في الوصف؟ لديك ما تضيفه؟ لا تتردد في مراسلتنا 👾