PT-2017-17383

CVE-2017-6868

·

Publicado

2017-07-07

·

Atualizado

2017-12-30

Descrição por

CVSS 3.1
8.1
Alta
MétricasAV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H
Name of the Vulnerable Software and Affected Versions Siemens SIMATIC CP 44x-1 RNA versions prior to 1.4.1
Description An issue with improper authentication was found, allowing an unauthenticated remote attacker to perform administrative actions on the Communication Process of the RNA series module. This is possible if network access to Port 102/TCP is available and the configuration file for the CP is stored on the RNA's CPU.
Recommendations For versions prior to 1.4.1, update to version 1.4.1 or later to resolve the issue. As a temporary workaround, consider restricting network access to Port 102/TCP and ensuring the configuration file for the CP is not stored on the RNA's CPU to minimize the risk of exploitation.
Explorabilidade
Correção
Impactos
Fornecedores
Produtos afetados
Enumeração de fraquezas
Identificadores relacionados
Encontrou algum problema na descrição? Tem algo a acrescentar? Fique à vontade para nos escrever 👾