PT-2018-2566 · Siemens · Simatic S7-400 Cpu 416-2 Dp V7+14
CVE-2018-16556
·
Publicado
2018-11-13
·
Atualizado
2023-05-09
CVSS v2.0
7.8
Alta
| Vetor | AV:N/AC:L/Au:N/C:N/I:N/A:C |
Name of the Vulnerable Software and Affected Versions
SIMATIC S7-400 CPU 412-1 DP V7 (All versions)
SIMATIC S7-400 CPU 412-2 DP V7 (All versions)
SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3)
SIMATIC S7-400 CPU 414-2 DP V7 (All versions)
SIMATIC S7-400 CPU 414-3 DP V7 (All versions)
SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3)
SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3)
SIMATIC S7-400 CPU 416-2 DP V7 (All versions)
SIMATIC S7-400 CPU 416-3 DP V7 (All versions)
SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3)
SIMATIC S7-400 CPU 416F-2 DP V7 (All versions)
SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3)
SIMATIC S7-400 CPU 417-4 DP V7 (All versions)
SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions)
SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9)
SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions)
SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1)
SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3)
SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3)
SIPLUS S7-400 CPU 416-3 V7 (All versions)
SIPLUS S7-400 CPU 417-4 V7 (All versions)
Description
The issue is related to errors in input validation by the Ethernet, PROFIBUS, and MPI interfaces, which could allow a remote attacker to cause a denial of service condition by sending specially crafted packets to port 102/tcp. This can cause the affected devices to go into defect mode, requiring a manual reboot to resume normal operation. No user interaction or privileges are required for exploitation.
Recommendations
For SIMATIC S7-400 CPU 412-1 DP V7 and other affected versions with no specified fix, at the moment, there is no information about a newer version that contains a fix for this vulnerability.
For SIMATIC S7-400 CPU 414-3 PN/DP V7 and SIPLUS S7-400 CPU 414-3 PN/DP V7, consider updating to version V7.0.3 or later.
For SIMATIC S7-400 H V6 CPU family, consider updating to version V6.0.9 or later.
For SIMATIC S7-410 CPU family, consider updating to version V8.2.1 or later.
As a temporary workaround, consider restricting access to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) to minimize the risk of exploitation.
RCE
Encontrou algum problema na descrição? Tem algo a acrescentar? Fique à vontade para nos escrever 👾
Enumeração de Fraquezas
Identificadores relacionados
Produtos afetados
Simatic S7-400 Cpu 412-1 Dp V7
Simatic S7-400 Cpu 412-2 Pn V7
Simatic S7-400 Cpu 414-2 Dp V7
Simatic S7-400 Cpu 414F-3 Pn/Dp V7
Simatic S7-400 Cpu 416-2 Dp V7
Simatic S7-400 Cpu 416-3 Pn/Dp V7
Simatic S7-400 Cpu 417-4 Dp V7
Simatic S7-400 H V4.5
Simatic S7-400 V6
Simatic S7-400 Pn/Dp V6
Simatic S7-410
Siplus S7-400 Cpu 414-3 Pn/Dp V7
Siplus S7-400 Cpu 416-3 Pn/Dp V7
Siplus S7-400 Cpu 416-3 V7
Siplus S7-400 Cpu 417-4 V7