PT-2013-3927
CVE-2013-2784
·
Published
2013-07-10
·
Updated
2013-07-11
Description by
CVSS 2.0
7.8
HighMetricsAV:N/AC:L/Au:N/C:N/I:N/A:C
Name of the Vulnerable Software and Affected Versions
Triangle Research International (aka Tri) Nano-10 PLC devices with firmware before r81
Description
The issue is related to an incorrect algorithm used for bounds checking of data in Modbus/TCP packets. This allows remote attackers to cause a denial of service, resulting in a networking outage, by sending a crafted packet to TCP port 502.
Recommendations
For Triangle Research International (aka Tri) Nano-10 PLC devices with firmware before r81, update the firmware to version r81 or later to resolve the issue. As a temporary workaround, consider restricting access to TCP port 502 to minimize the risk of exploitation.