PT-2016-5774

CVE-2016-3949

·

Published

2016-06-27

·

Updated

2020-02-10

Description by

CVSS 2.0
7.8
High
MetricsAV:N/AC:L/Au:N/C:N/I:N/A:C
Name of the Vulnerable Software and Affected Versions Siemens SIMATIC S7-300 Profinet-enabled CPU devices versions prior to 3.2.12 Siemens SIMATIC S7-300 Profinet-disabled CPU devices versions prior to 3.3.12
Description The issue allows remote attackers to cause a denial of service, resulting in a defect-mode transition. This can be achieved via crafted packets, specifically (1) ISO-TSAP or (2) Profibus packets.
Recommendations For Siemens SIMATIC S7-300 Profinet-enabled CPU devices versions prior to 3.2.12, update the firmware to version 3.2.12 or later. For Siemens SIMATIC S7-300 Profinet-disabled CPU devices versions prior to 3.3.12, update the firmware to version 3.3.12 or later.
Exploitability
Fix
Vendors
Affected products
Weakness enumeration
Related identifiers
Found an issue in the description? Have something to add? Feel free to write us 👾