PT-2017-19306

CVE-2017-9945

·

Published

2017-08-30

·

Updated

2017-09-12

Description by

CVSS 3.1
6.5
Medium
MetricsAV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Name of the Vulnerable Software and Affected Versions Siemens 7KM PAC Switched Ethernet PROFINET expansion module versions prior to V2.1.3
Description A Denial-of-Service condition could be induced by a specially crafted PROFINET DCP packet sent as a local Ethernet (Layer 2) broadcast. The affected component requires a manual restart via the main device to recover.
Recommendations For versions prior to V2.1.3, update to version V2.1.3 or later to resolve the issue. As a temporary workaround, consider restricting access to the local Ethernet (Layer 2) broadcast to minimize the risk of exploitation.