PT-2022-5036 · Hitachi Energy · Hitachi Energy Microscada X Sys600

CVE-2022-29492

·

Published

2022-04-29

·

Updated

2022-10-05

CVSS v2.0

7.8

High

VectorAV:N/AC:L/Au:N/C:N/I:N/A:C
Name of the Vulnerable Software and Affected Versions Hitachi Energy MicroSCADA Pro SYS600 versions 9.0 through 9.4 FP2 Hotfix 4 Hitachi Energy MicroSCADA X SYS600 versions 10 through 10.3.1
Description The issue is caused by improper input validation in the handling of a malformed IEC 104 TCP packet. Upon receiving a malformed packet, the packet is dropped, but the TCP connection is left open, potentially causing a denial-of-service if the affected connection is left open.
Recommendations For Hitachi Energy MicroSCADA Pro SYS600 versions 9.0 through 9.4 FP2 Hotfix 4, update to a version later than 9.4 FP2 Hotfix 4. For Hitachi Energy MicroSCADA X SYS600 versions 10 through 10.3.1, update to a version later than 10.3.1. As a temporary workaround, consider restricting access to the IEC 104 TCP connection to minimize the risk of exploitation.

Fix

Improper Resource Release

RCE

Found an issue in the description? Have something to add? Feel free to write us 👾

Weakness Enumeration

Related Identifiers

BDU:2022-06256
CVE-2022-29492

Affected Products

Hitachi Energy Microscada X Sys600