PT-2023-4235

CVE-2022-2502

·

Published

2023-07-26

·

Updated

2026-11-10

Description by

CVSS 2.0
7.8
High
MetricsAV:N/AC:L/Au:N/C:N/I:N/A:C
Name of the Vulnerable Software and Affected Versions Hitachi Energy RTU500 series product (affected versions not specified)
Description The issue is related to a buffer overflow in the stack of the HCI interface, which functions according to the IEC 60870-5-104 standard. This can be exploited by an attacker to cause a denial of service. The vulnerability can only be exploited if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’. An attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually, if exploited, causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Recommendations At the moment, there is no information about a newer version that contains a fix for this vulnerability.
Impacts
Vendors
Affected products
Related identifiers
Found an issue in the description? Have something to add? Feel free to write us 👾