PT-2026-146047

CVE-2026-47711

·

Published

2026-11-12

·

Updated

2026-11-12

Description by

CVSS 3.1
8.6
High
MetricsAV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H
Name of the Vulnerable Software and Affected Versions BACnet Stack versions prior to 1.4.4 BACnet Stack versions prior to 1.5.1 BACnet Stack versions prior to 1.6.0
Description The master demo server can be crashed remotely via BACnet/IP. This occurs when a valid Confirmed WriteProperty request is sent to update the controlled-variable-reference of loop-1 to point to life-safety-zone-1 / accepted-modes.
Recommendations Update to version 1.4.4 Update to version 1.5.1 Update to version 1.6.0
Exploitability
Exploit
Fix
Impacts
Vendors
Affected products
Related identifiers
GHSA-VRPM-9GM2-X552