PT-2026-58040 · Rockwell Automation · Factorytalk Services Platform
CVE-2026-10714
·
Published
2026-07-14
·
Updated
2026-07-14
CVSS v4.0
8.8
High
| Vector | AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
Name of the Vulnerable Software and Affected Versions
FactoryTalk Services Platform (affected versions not specified)
Description
An issue in the FactoryTalk Services Platform allows an attacker to bypass JWT (JSON Web Token) signature validation during Okta Web Authentication. The flaw occurs because the application fails to verify that the JWT algorithm is configured for RSA, allowing an attacker to set the algorithm to
none and create forged tokens. This enables an authenticated low-privilege user to impersonate any authorized user on the server, leading to unauthorized access to system configuration and the ability to grant permissions to other systems protected by the platform.Recommendations
At the moment, there is no information about a newer version that contains a fix for this vulnerability.
Found an issue in the description? Have something to add? Feel free to write us 👾
Weakness Enumeration
Related Identifiers
Affected Products
Factorytalk Services Platform